Du/Pu Monitor Display Selection - Mitsubishi Electric FR-F740 EC Instruction Manual

Fr-f700 series
Table of Contents

Advertisement

Monitor display and monitor output signals
6.10.2
DU/PU monitor display selection (Pr. 52, Pr. 54, Pr. 158, Pr. 170, Pr. 171,
Pr. 268, Pr. 563, Pr. 564, Pr. 891)
The monitor to be displayed on the main screen of the operation panel (FR-DU07)/parameter
unit (FR-PU04/FR-PU07) can be selected.
Pr.
Name
No.
DU/PU main display data
52
selection
CA terminal function
54
selection
AM terminal function
158
selection
170
Watt-hour meter clear
Operation hour meter
171
clear
Monitor decimal digits
268
selection
Energizing time
563
carrying-over times
Operating time carrying-
564
over times
Cumulative power
891
monitor digit shifted
times
The above parameters can be set when Pr. 160 = 0.
The above parameters allow its setting to be changed during operation in any operation
mode even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
6 - 138
Initial
Setting
Description
Value
Range
0/5/6/
Select the monitor to be displayed on the
8–14/17/
0
operation panel and parameter unit.
20/23–25/
(output
50–57/64/
Refer to Tab. 6-23 for monitor descrip-
frequency)
67/81–86/
tion.
100
1–3/5/6/
8–14/17/
21/24/50/
Select the monitor output to terminal CA.
52/53/67/
1
70/85
(output
1–3/5/6/
frequency)
8–14/17/
21/24/50/
Select the monitor output to terminal AM.
52/53/67/
70/86
Set "0" to clear the watt-hour meter
0
monitor.
Set the maximum value when monitoring
9999
10
from communication to 0 to 9999kWh.
Set the maximum value when monitoring
9999
from communication to 0 to 65535kWh.
Set "0" in the parameter to clear the watt-
9999
0/9999
hour monitor.
Setting "9999" has no effect.
0
Displays as integral value.
9999
1
Displayed in 0.1 increments.
9999
No function
The numbers of cumulative energizing
0–65535
time monitor exceeded 65535h is dis-
0
(reading
played.
only)
Reading only
0–65535
The numbers of operation time monitor
0
(reading
exceeded 65535h is displayed. Reading
only)
only
Set the number of times to shift the
0–4
cumulative power monitor digit.
Clamp the monitoring value at maximum.
9999
No shift
9999
Clear the monitor value when it exceeds
the maximum value.
Parameter
Refer to
Parameters referred to
Section
37
Speed display
6.10.1
144
Speed setting
6.10.1
switchover
55
Frequency
6.10.3
monitoring
reference
56
Current
6.10.3
monitoring
reference