Mitsubishi Electric FR-F740 EC Instruction Manual page 484

Fr-f700 series
Table of Contents

Advertisement

PID control
Connection diagram
The following graphic shows a typical application:
Pr. 128 = 20
Pr. 183 = 14
Pr. 191 = 47
Pr. 192 = 16
Pr. 193 = 14
Pr. 194 = 15
Forward rotation
Reverse rotation
Potentiometer
1kΩ, 1–2W
(Set point
Fig. 6-180: Connection diagram in source logic
The power supply must be selected in accordance with the power specifications of the
detector used.
The used input signal terminal changes depending on the Pr. 178 to Pr. 189 "Input terminal
selection" setting.
The used output signal terminal changes depending on the Pr. 190 to Pr. 196 "Output
terminal selection" setting.
The AU signal need not be input.
6 - 334
Power
supply
PID control
selection
Setting
setting)
1 phase,
e.g. 230V, 50Hz
U
L1
L2
V
L3
W
STF
STR
RT (X14)
During PID action (PID)
SU
PC
Upper limit (FUP)
FU
10
Lower limit (FDN)
OL
Forward/reverse rotation
2
IPF
(RL)
SE
Power supply for OC
5
outputs
1
4
Measured value 4–20 mA
0
24V
Parameter
Pump
M
P
2 wire type
+
-
I001328C

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-f746 ec

Table of Contents