Operation mode (Pr. 79)

5.7
Operation mode (Pr. 79)
Select the operation command location and frequency command location.
Pr.
Initial
Name
No.
Value
Operation
79
mode
0
selection
For the terminal used for the X12 signal (PU operation interlock signal) input, assign "12" in
Pr. 178 to Pr. 189 "input terminal function selection" to assign functions. For Pr. 178 to
Pr. 189, refer to section 6.9.1. When the X12 signal is not assigned, function of the MRS
signal switches from MRS (output stop) to PU operation interlock signal.
NOTES
Use the simple setting mode to set Pr. 79 in simple steps.
If switching of the operation mode is invalid even though Pr. 79 is set, check the related
notes of troubleshooting (refer to section 7.6.9).
5 - 12
Setting
Description
Range
External/PU switch over mode
Press the PU/EXT key to switch between the PU and external operation
mode. (Refer to section 4.5.)
0
At power ON, the inverter is in the external operation mode.
Operation mode
PU operation mode
1
(fixed)
Fixed to external opera-
tion mode
Operation can be per-
2
formed by switching
between the external
and Net operation
mode.
External/PU combined
3
operation mode 1
External/PU combined
4
operation mode 2
Switch-over mode
6
Switch among PU operation, external operation, and NET operation while
keeping the same operation status.
External operation mode (PU operation interlock)
X12 signal ON
: Operation mode can be switched to the PU operation
7
mode (output stop during external operation)
X12 signal OFF : Operation mode can not be switched to the PU opera-
tion mode.
Running frequency
Start signal
Input from the PU
Setting by PU
(FWD/REV keys)
(FR-DU07/FR-PU04/
(FR-DU07/FR-PU04/
FR-PU07)
FR-PU07)
External signal input
(Terminal 2, 4, 1, JOG,
External signal input
(terminal STF-, STR)
multi-speed selection,
etc.)
PU (FR-DU07/
FR-PU04/FR-PU07)
setting or external
signal input (multi-
External signal input
(terminal STF-, STR)
speed setting, across
terminals 4-5 (valid
when AU signal turns
on).
External signal input
Input from the PU
(Terminal 2, 4, 1, JOG,
(FWD/REV keys)
(FR-DU07/FR-PU04/
multi-speed selection,
FR-PU07)
etc.)
Basic settings
LED Indication
: OFF
: ON
PU operation mode
External operation mode
NET operation mode
PU operation mode
External operation mode
NET operation mode
Combined operation mode
PU operation mode
External operation mode
NET operation mode