Parameter
Parameter
Func-
Name
tion
Terminal 2 frequency
125
setting gain frequency
Terminal 4 frequency
126
setting gain frequency
Analog input display
241
unit switch over
Terminal 2 frequency
C2
setting bias frequency
(902)
Terminal 2 frequency
C3
setting bias
(902)
Terminal 2 frequency
C4
setting gain
(903)
Terminal 4 frequency
C5
setting bias frequency
(904)
Terminal 4 frequency
C6
setting bias
(904)
Terminal 4 frequency
C7
setting gain
(905)
PID control automatic
127
switchover frequency
128
PID action selection
Tab. 6-1:
Parameter overview (15)
FR-F700 EC
Incre-
Initial
Setting
ments
Value
Range
0.01Hz
50Hz
0–400Hz
0.01Hz
50Hz
0–400Hz
0
1
0
1
0.01Hz
0Hz
0–400Hz
0.1%
0%
0–300%
0.1%
100%
0–300%
0.01Hz
0Hz
0–400Hz
0.1%
20%
0–300%
0.1%
100%
0–300%
0–400Hz
0.01Hz
9999
9999
10, 110
11, 111
20, 120
21, 121
40, 140
41, 141
50
51
60
1
10
61
70
71
80
81
90
91
100
101
Description
Set the frequency of terminal 2 input
gain (maximum).
Set the frequency of terminal 4 input
gain (maximum).
Displayed in %
Select the unit for
analog input dis-
Displayed in V/mA
play.
Set the frequency on the bias side of
terminal 2 input.
Set the converted % of the bias side
voltage (current) of terminal 2 input.
Set the converted % of the gain side
voltage of terminal 2 input.
Set the frequency on the bias side of
terminal 4 input.
Set the converted % of the bias side
current (voltage) of terminal 4 input.
Set the converted % of the gain side
current (voltage) of terminal 4 input.
Set the frequency at which the con-
trol is automatically changed to PID
control.
Without PID automatic switchover
function
PID reverse action Deviation value
signal
PID forward action
(terminal 1)
PID reverse action Measured value
(terminal 4)
Set point (termi-
PID forward action
nal 2 or Pr. 133)
PID reverse action Measured value
(terminal 4)
Set point input
(LonWorks, CC-
PID forward action
Link communica-
tion, BACnet)
PID reverse action Deviation value
signal input
(LonWorks, CC-
PID forward action
Link communica-
tion, BACnet
)
PID reverse action Measured value,
set point input
(LonWorks, CC-
PID forward action
Link communica-
tion, BACnet)
PID reverse action Deviation value
signal input:
PID forward action
PLC function
PID reverse action Measured value,
set point input:
PID forward action
PLC function
PID reverse action Deviation value
signal input:
PLC function
PID forward action
(Not applied to the
inverter frequency)
PID reverse action Measured value,
set point input:
PLC function
PID forward action
(Not applied to the
inverter frequency)
Parameter overview
All
Para-
Para-
para-
meter
meter
meter
copy
clear
Refer
clear
to
page
✔: enabled
—: disabled
6-199
6-328
6 - 15