Mitsubishi Electric FR-F740 EC Instruction Manual page 469

Fr-f700 series
Table of Contents

Advertisement

Parameter
● Binary Output
Object
Identifier
0
1
2
3
4
5
6
Tab. 6-104: Object assignment for binary outputs
/v: Read/Write (Commandable values supported)
Available regardless of operation mode, operation command source and speed command
source.
● Binary Value
Object
Identifier
0
11
98
99
200
300
301
302
303
304
305
306
307
Tab. 6-105: Object assignment for binary values (1)
FR-F700 EC
Present
Object Name
Value Access
Type
Terminal RUN CMD
Terminal SU CMD
Terminal IPF CMD
Terminal OL CMD
Terminal FU CMD
Terminal ABC1 CMD
Terminal ABC2 CMD
Present
Object Name
Value Access
Type
Inverter running
Inverter operation
ready
Alarm output
Fault output
Inverter running
reverse
Control input
instruction AU
Control input
instruction RT
Control input
instruction RL
Control input
instruction RM
Control input
instruction RH
Control input
instruction JOG
Control input
instruction MRS
Control input
instruction STOP
Communication operation and setting
Description (0: Inactive, 1: Active)
Controls actual output of terminal RUN.
/v
Available when Pr. 190 = "82 or 182".
Controls actual output of terminal SU.
/v
Available when Pr. 191 = "82 or 182".
Controls actual output of terminal IPF.
/v
Available when Pr. 192 = "82 or 182".
Controls actual output of terminal OL.
/v
Available when Pr. 193 = "82 or 182".
Controls actual output of terminal FU.
/v
Available when Pr. 194 = "82 or 182".
Controls actual output of terminal ABC1.
/v
Available when Pr. 195 = "82 or 182".
Controls actual output of terminal ABC2.
/v
Available when Pr. 196 = "82 or 182".
Description
Represents inverter running (RUN signal) status.
Represents inverter operation ready (RY signal) status.
Represents alarm output (LF signal) status.
Represents fault output (ALM signal) status.
Represents inverter reverse running status.
Controls the function assigned to terminal AU.
/v
Setting 1 of this object turns ON the signal assigned to
Pr. 184.
Controls the function assigned to terminal RT. Setting 1 of
/v
this object turns ON the signal assigned to Pr. 183.
Controls the function assigned to terminal RL.
/v
Setting 1 of this object turns ON the signal assigned to
Pr. 180.
Controls the function assigned to terminal RM.
/v
Setting 1 of this object turns ON the signal assigned to
Pr. 181.
Controls the function assigned to terminal RH.
/v
Setting 1 of this object turns ON the signal assigned to
Pr. 182.
Controls the function assigned to terminal JOG.
/v
Setting 1 of this object turns ON the signal assigned to
Pr. 185.
Controls the function assigned to terminal MRS.
/v
Setting 1 of this object turns ON the signal assigned to
Pr. 187.
Controls the function assigned to terminal STOP.
/v
Setting 1 of this object turns ON the signal assigned to
Pr. 188.
6 - 319