Mitsubishi Electric FR-F740 EC Instruction Manual page 184

Fr-f700 series
Table of Contents

Advertisement

Parameter overview
Parameter
Func-
Name
tion
Second pre-charge
765
fault selection
Second pre-charge
766
ending level
Second pre-charge
767
ending time
Second pre-charge
768
upper detection level
Second pre-charge
769
time limit
PU/DU monitor
774
selection 1
PU/DU monitor
775
selection 2
PU/DU monitor
776
selection 3
777
Refer to Pr. 73
778
779
Refer to Pr. 502
Pulse increment set-
799
ting for output power
826
Refer to Pr. 414 and Pr. 415
865
867
Refer to Pr. 54 to Pr. 56
869
870
Refer to Pr. 41–Pr. 43
872
Refer to Pr. 251
Tab. 6-1:
Parameter overview (34)
6 - 34
Incre-
Initial
Setting
ments
Value
Range
0
1
0%
1
0–100%
0.1%
9999
9999
0–3600s
0.1s
9999
9999
0–100%
0.1%
9999
9999
0–3600s
0.1s
9999
9999
1– 3/5/6/
8 –14/17/
20/23– 25/
1
9999
40–42/
50 –57/64/
67/81–86/
100/9999
0.1/1/10/
0.1
1kWh
100/
1000kWh
Description
When the pre-charged amount
exceeds Pr. 768 or the pre-
charged time exceeds Pr. 769
while the RT signal is ON, the out-
put is immediately shutoff, and the
fault (E.PCH) is output.
When the pre-charged amount
exceeds Pr. 768 or the pre-
charged time exceeds Pr. 769
while the RT signal is ON, the
motor decelerates to stop, and the
fault (E.PCH) is output.
Set the measurement level to end
the pre-charge operation, which is
performed while the RT signal is
ON.
Without second pre-charge ending
level
Set the time to end the pre-charge
operation, which is performed
while the RT signal is ON.
Without second pre-charge ending
time
Set the upper limit for the pre-
charged amount, which is charged
while the RT signal is ON. If the
pre-charged amount exceeds the
set level, the fault (E.PCH) is out-
put.
Without second pre-charge ending
level
Set the time limit for the pre-
charge operation, which is per-
formed while the RT signal is ON.
If the pre-charged time exceeds
the set level, the fault (E.PCH) is
output.
Without second pre-charge time
limit
Select the monitored item to be
displayed on the first monitor (first
row in the 3-line monitor).
Select the monitored item to be
displayed on the second monitor
(second row in the 3-line moni-
tor).
Select the monitored item to be
displayed on the third monitor
(third row in the 3-line monitor).
Pulse train output of output power
(Y79) is output in pulses at every
output power (kWh) that is
specified.
Parameter
All
Para-
Para-
para-
meter
meter
meter
copy
clear
Refer
clear
to
page
✔: enabled
—: disabled
6-350
6-358
6-358
6-416
6-135

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-f746 ec

Table of Contents