Parameter
Specify operation mode at power on (Pr. 340)
Depending on the Pr. 79 and Pr. 340 settings, the operation mode at power on (reset) changes
as described below:
Pr. 340
0
(initial
value)
1 / 2
10 / 12
Tab. 6-49:
The Pr. 340 setting "2" or "12" is mainly used for communication operation using the inverter
RS485 terminals. When Pr. 57 "Restart coasting time" ≠ 9999 (selection of automatic restart
after instantaneous power failure), the inverter will resume the same operation state which
was in before after power has been restored from an instantaneous power failure.
The operation mode cannot be switched directly between the PU operation mode and
network operation mode.
Operation mode can be changed between the PU operation mode and network operation
mode with the PU/EXT key of the operation panel (FR-DU07) and X65 signal.
FR-F700 EC
Operation Mode at Power on,
Pr. 79
Power Restoration, Reset
0
(initial
External operation mode
value)
1
PU operation mode
2
External operation mode
3 / 4
External/PU combined operation mode
6
External operation mode
X12 (MRS) signal ON: External operation
mode
7
X12 (MRS) signal OFF: External operation
mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
3 / 4
External/PU combined operation mode
6
NET operation mode
X12 (MRS) signal ON: NET operation mode
7
X12 (MRS) signal OFF: External operation
mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
3 / 4
External/PU combined operation mode
6
NET operation mode
7
External operation mode
Operation mode of the inverter at power on
Selection of operation mode and operation location
Operation Mode Switching
Can be switched to external, PU or NET
operation mode
Fixed to PU operation mode
Can be switched to external or NET opera-
tion mode
Switching to PU operation mode disabled
Operation mode switching disabled
Can be switched to external, PU or NET
operation mode with operation continued
Can be switched to external, PU or NET
operation mode
Fixed to external operation mode (Forcibly
switched to external operation mode.)
Same as when Pr. 340 = 0
Can be switched to PU or NET operation
mode
Same as when Pr. 340 = 0
Fixed to NET operation mode
Same as when Pr. 340 = 0
Can be switched to PU or NET operation
mode with operation continued
Same as when Pr. 340 = 0
6 - 243