Mitsubishi Electric FR-F740 EC Instruction Manual page 399

Fr-f700 series
Table of Contents

Advertisement

Parameter
Selection of control source in network operation mode (Pr. 338, Pr. 339)
As control sources, there are the operation command sources that control the signals related to
the inverter start command and function selection and the speed command source that controls
the signals related to frequency setting.
In network operation mode, the commands from the external terminals and communication (in-
verter RS485 terminals or communication option) are as listed below.
Communication operation
command source (Pr. 338)
Operation
Location
Communication speed
Selection
command source (Pr.339)
Fixed
Running frequency from
function
communication
(Terminal-
Terminal 2
equivalent
function)
Terminal 4
Terminal 1
Low speed operation
0
RL
command/remote setting clear
Middle-speed operation
1
RM
command/remote setting
deceleration
High speed operation
2
RH
command/remote setting
acceleration
3
RT
Second function selection
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
Selection of automatic restart
6
CS
after instantaneous power
failure
7
OH
External thermal relay input
Fifteen speed selection
8
REX
Inverter operation enable
10
X10
signal
FR-HC or MT-HC connection,
11
X11
instantaneous power failure
detection
PU operation external
12
X12
interlock
External DC injection brake
13
X13
operation is started
14
X14
PID control valid terminal
PU-external operation
16
X16
switchover
Tab. 6-53:
Writing operation and speed commands (1)
FR-F700 EC
Selection of operation mode and operation location
0: NET
1:
2:
0: NET
Exter-
Exter-
nal
nal
NET
NET
External
External
Compensation
NET
External
NET
External
NET
External
NET
Combined
External
External
NET
External
External
External
External
NET
NET
External
External
1: External
1:
2:
0: NET
Exter-
Exter-
nal
nal
NET
NET
External
External
NET
External
NET
External
NET
External
External
Combined
External
NET
External
External
NET
External
Remarks
Pr. 59 = 0
(multi-speeds)
Pr. 59 = 1, 2
(remote)
Pr. 59 = 0