3.4.13 DU/PU, terminal FM/AM monitor display selection (Pr. 46 to Pr. 48, Pr. 50, Pr. 52, Pr. 54)

The monitor to be displayed on the main screen of the operation panel (FR-DU07-CNV)/parameter unit (FR-PU07) can
be selected.
In addition, signals to be output from the terminal FM (pulse train output) and AM (analog voltage output) can be
selected.
Parameter
Number
46
Watt-hour meter clear
47
Energization time carrying-over times
Cumulative power monitor digit shifted
48
times
50
AM terminal function selection
52
DU/PU main display data selection
54
FM terminal function selection
(1) Monitor description list (Pr. 52)
 Set the monitor to be displayed on the operation panel (FR-DU07-CNV) and parameter unit (FR-PU07) in Pr. 52 DU/PU
main display data selection.
 Set the monitor to be output to the terminal FM (pulse train output) in Pr. 54 FM terminal function selection
 Set the monitor to be output to the terminal AM (0 to 10VDC analog voltage output) in Pr. 50 AM terminal function selection
 Refer to the following table and set the monitor to be displayed. (The signals marked  cannot be selected for monitoring)
Types of Monitor
Input current
Input voltage
Bus voltage
Fault display
Power supply frequency
Electronic thermal relay
load factor
Input power
Cumulative power

Cumulative energization
time

Input power (with
regenerative display)
Reference voltage output
Input terminal status
Output terminal status
86
Name
Initial value
Pr. 52 Setting
PU
Increments
DU LED
main
monitor
0.01A/0.1A
0

0.1V
0
0.1V
0
0
0.01Hz
5
0.1%
6
0.01kW/
7
0.1kW

0.01kWh/
8
0.1kWh

1h
9
0.1kW/1kW
10


25
Setting range
0
10
9999
9999
0 to 65535
0
(Reading only)
0 to 4
9999
9999
1 to 3, 5, 6, 7, 21,
1234
1111 to 4444
0, 5 to 10, 25,
1234
1111 to 4444
1 to 3, 5, 6, 7, 21,
1234
1111 to 4444
Full-scale
Pr. 54 (FM)
Value of the
Pr. 50 (AM)
Terminal FM
Setting
and AM
1
Pr. 56
2
Pr. 53
3
Pr. 55

5
Pr. 49
6
100%
7
Pr. 51
21
Description
Set "0" to clear the watt-hour meter monitor.
Set the maximum value in the range of 0 to
9999kWh for the monitoring from communication
Set the maximum value in the range of 0 to
65535kW for the monitoring from communication.
Displays the numbers of times that the
cumulative energization time monitor exceeded
65535h. Reading only
Set the number of times to shift the cumulative
power monitor digit.
The monitor value is clamped at the maximum
value.
No shift
The monitor value is cleared when it exceeds the
maximum value.
Select the monitor output to terminal AM.
Select the monitor to be displayed on the
operation panel and parameter unit.
Refer to the following table for monitor
description.
Select the monitor output to terminal FM.
Description
Displays the converter input current.
Displays the converter input voltage
effective value.
Displays the converter output voltage.
Displays 8 past faults individually.
Displays power supply frequency.
Displays the motor thermal cumulative value by
regarding the thermal operation level as 100%.
Displays the converter input power.
Displays the cumulative power based on the
input power monitor.
Can be cleared by Pr. 46 (Refer to page 87)
Displays the cumulative energization time
since the converter shipment.
You can check how many times the monitor
value exceeded 65535h with Pr. 47.
Displays the converter input power
The value is displayed with "-" (minus sign)
during the regenerative driving.
Terminal FM: 1440 pulse/s is output.
Terminal AM: 10V is output.
Displays the input terminal ON/OFF status
on the operation panel (Refer to page 87)