4.11.2 Monitor display selection of DU/PU and terminal FM
(Pr. 52, Pr. 54, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891)
The monitor to be displayed on the main screen of the operation panel and parameter unit (FR-PU04/FR-PU07) can be
selected.
In addition, signal to be output from the terminal FM (pulse train output) can be selected.
Parameter
Name
Number
DU/PU main display data
52 ∗
selection
FM terminal function
54 ∗
selection
170
Watt-hour meter clear
171
Operation hour meter clear
Monitor decimal digits
268 ∗
selection
Energization time carrying-
563
over times
Operating time carrying-
564
over times
Cumulative power monitor
891 ∗
digit shifted times
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 163)
∗ This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
(1)
Monitor description list (Pr. 52)
Set the monitor to be displayed on the operation panel and parameter unit (FR-PU04/FR-PU07) in Pr. 52 DU/PU main
display data selection .
Set the monitor to be output to the terminal FM (pulse train output) in Pr. 54 FM terminal function selection .
Refer to the following table and set the monitor to be displayed. (The monitor marked with × cannot be selected.)
Types of Monitor
Unit
Output frequency ∗7
0.01Hz
Output current ∗7
0.01A
Output voltage ∗7
0.1V
Fault display
Frequency setting
0.01Hz
value
Monitor display and monitor output signal
Initial Value
0
(output
frequency)
1
(output
frequency)
9999
9999
9999
0
0
9999
Pr. 52 Setting
Operation
PU
Pr. 54 (FM)
panel
main
Setting
LED
monitor
0/100
1
0/100
2
0/100
3
×
0/100
∗1
5
5
Setting Range
Select the monitor to be displayed on the
0, 5, 8 to 12, 14, 20,
operation panel and parameter unit.
23 to 25, 52 to 55,
Refer to the following table for monitor
61, 62, 64, 100
description.
1 to 3, 5, 8 to 12,
14, 21, 24, 52, 53,
Select the monitor output to terminal FM.
61, 62
0
Set "0" to clear the watt-hour meter monitor.
Sets the maximum value for monitoring from
10
communication to 9999kWh.
Sets the maximum value for monitoring from
9999
communication to 65535kWh.
Set "0" in the parameter to clear the operation
0, 9999
time monitor.
Setting 9999 does not clear.
0
Displayed as integral value
1
Displayed in 0.1 increments
9999
No function
The numbers of cumulative energization time
0 to 65535
monitor exceeded 65535h is displayed.
(reading only)
(Reading only)
0 to 65535
The numbers of operation time monitor
(reading only)
exceeded 65535h is displayed. (Reading only)
Set the number of times to shift the cumulative
0 to 4
power monitor digit.
Clamp the monitoring value at maximum.
No shift
9999
Clear the monitor value when it exceeds the
maximum value.
Terminal FM
Full Scale Value
Pr. 55
Displays the inverter output frequency.
Displays the inverter output current
Pr. 56
effective value.
100V class,
400V
200V class
Displays the inverter output voltage.
400V class 800V
Displays past 8 faults individually.
Pr. 55
Displays the set frequency.
Description
Description
129