Operation
4.5.5

Perform frequency setting by analog current input

● Pr. 79 "Operation mode selection" must be set to "4" (external/PU combined operation
mode 2).
● Turn the AU signal on.
● Use the FWD or REV key to give a start command.
Fig. 4-19: Frequency setting by analog current input
FR-F700 EC
Power
supply
AU signal
Output of the
adjustment meter
(0/4–20mADC)
PU operation mode
Inverter
Motor
I001078E