Cables And Wiring Length; Cable Size - Mitsubishi Electric FR-F740 EC Instruction Manual

Fr-f700 series
Table of Contents

Advertisement

Wiring

Cables and wiring length

Select the recommended cable size to ensure that a voltage drop will be 2% max.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop
will cause the motor torque to decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m.
400V class
(when input power supply is 440V based on a rated current for 110% overload for 1 minute)
Terminal
Applicable Inverter
Screw
Type
Size
FR-F740/746-00023 to
M4
00083-EC
FR-F740/746-00126-EC
M4
FR-F740/746-00170-EC
M4
FR-F740/746-00250-EC
M4
FR-F740/746-00310-EC
M5
FR-F740/746-00380-EC
M5
FR-F740/746-00470-EC
M6
FR-F740/746-00620-EC
M6
FR-F740/746-00770-EC
M6
FR-F740/746-00930-EC
M8
FR-F740/746-01160-EC
M8
FR-F740-01800-EC
M8 (M10)
FR-F740-02160-EC
M10
FR-F740-02600-EC
M10
FR-F740-03250-EC
M10 (M12)
FR-F740-03610-EC
M10 (M12)
FR-F740-04320-EC
M12 (M10)
FR-F740-04810-EC
M12 (M10)
FR-F740-05470-EC
M12 (M10)
FR-F740-06100-EC
M12 (M10)
FR-F740-06830-EC
M12 (M10)
FR-F740-07700-EC
M12 (M10)
FR-F740-08660-EC
M12 (M10)
FR-F740-09620-EC
M12 (M10)
FR-F740-10940-EC
M12 (M10)
FR-F740-12120-EC
M12 (M10)
Tab. 3-4:

Cable size

FR-F700 EC
Crimping
Tighten-
Terminal
ing
Torque
L1, L2,
U, V, W L1, L2,
[Nm]
L3
L3
1.5
2-4
2-4
1.5
2-4
2-4
1.5
5.5-4
5.5-4
3.5
1.5
5.5-4
5.5-4
5.5
2.5
8-5
8-5
2.5
14-5
8-5
14
4.4
14-6
14-6
14
4.4
22-6
22-6
22
4.4
22-6
22-6
22
7.8
38-8
38-8
38
7.8
60-8
60-8
60
7.8
60-8
60-8
60
14.7
100-10 100-10
80
14.7
100-10 100-10
100
14.7
150-10 150-10
125
14.7
150-10 150-10
150
100-12 100-12 2 × 100 2 × 100 2 × 100
24.5
100-12 100-12 2 × 100 2 × 100 2 × 100
24.5
150-12 150-12 2 × 125 2 × 125 2 × 125
46
150-12 150-12 2 × 150 2 × 150 2 × 125
46
200-12 200-12 2 × 200 2 × 200 2 × 150
46
C2-200 C2-200 2 × 200 2 × 200 2 × 200
46
C2-250 C2-250 2 × 250 2 × 250 2 × 250
46
C2-250 C2-250 2 × 250 2 × 250 2 × 250
46
C2-200 C2-200 3 × 200 3 × 200 3 × 200
46
C2-200 C2-200 3 × 200 3 × 200 3 × 200
46
HIV, etc. [mm²]
Earth
U, V, W P/+, P1
cable
gauge
2
2
2
2
2
2
3.5
3.5
3.5
3.5
3.5
5.5
5.5
8
8
8
8
8
8
14
14
14
22
14
22
22
14
22
22
14
38
38
22
60
60
22
60
60
38
80
80
38
100
100
38
125
100
38
150
150
38
38
38
38
60
60
60
60
100
100
100
Main circuit connection
Cable Size
AWG
PVC, etc. [mm²]
L1, L2,
U, V, W L1, L2,
U, V, W
L3
L3
14
14
2.5
12
14
2.5
12
12
4
10
10
6
8
8
10
6
8
16
6
6
16
4
4
25
4
4
25
1
2
50
1/0
1/0
50
1/0
1/0
50
3/0
3/0
70
4/0
4/0
95
250
250
120
300
300
150
2 × 4/0 2 × 4/0
2 × 95
2 × 95
2 × 4/0 2 × 4/0
2 × 95
2 × 95
2 × 250 2 × 250 2 × 120 2 × 120
2 × 300 2 × 300 2 × 150 2 × 150
2 × 350 2 × 350 2 × 185 2 × 185 2 × 95
2 × 400 2 × 400 2 × 185 2 × 185 2 × 95
2 × 500 2 × 500 2 × 240 2 × 240 2 × 120
2 × 500 2 × 500 2 × 240 2 × 240 2 × 120
3 × 350 3 × 350 3 × 185 3 × 185 2 × 150
3 × 400 3 × 400 3 × 185 3 × 185 2 × 150
Earth
cable
gauge
2.5
2.5
2.5
4
4
4
6
10
10
10
10
16
16
16
25
16
25
16
50
25
50
25
50
25
70
35
95
50
120
70
150
95
95
95
120
150
3 - 11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-f746 ec

Table of Contents