Communication operation and setting
6.18.9
Protocol Implementation Conformance Statement – PICS
(This section 6.18.9 is part of this Standard and is required for its use.)
BACnet Protocol Implementation Conformance Statement
Date:
Vendor name:
Vendor ID:
Product name:
Product model number:
Application software version:
Firmware revision:
BACnet protocol revision:
BACnet standardized device profile: BACnet Application Specific Controller (B-ASC)
BACnet Interoperability Building Blocks supported (BIBBs):
Data Sharing - ReadProperty-B (DS-RP-B)
Data Sharing - WriteProperty-B (DS-WP-B)
Device Management - DynamicDeviceBinding-B (DM-DDB-B)
Device Management - DynamicObjectBinding-B (DM-DOB-B)
Device Management - DeviceCommunicationControl-B (DM-DCC-B)
Device Management - ReinitializeDevice - B (DM-RD-B)
Segmentation capability:
Standard object types supported: Refer to Tab. 6-99 for the supported object types and
Object editing:
Data link layer options:
Device address binding:
Networking options:
Character sets supported:
6 - 326
1st Apr 2012
Mitsubishi Electric Corporation
—
Inverter
FR-F740-EC
8290A
1.00
4
No
their properties of FR-F700-EC series.
Dynamic CreateObject service and DeleteObject ser-
vice are not supported.
MS/TP master (Clause 9),
baud rate(s): 9600, 19200, 38400, 76800
Static device binding is not supported.
None
ANSI X3.4
Parameter