Control Circuit Terminals - Mitsubishi Electric FR-F740 EC Instruction Manual

Fr-f700 series
Table of Contents

Advertisement

Wiring
3.4.1

Control circuit terminals

Fig. 3-8: Terminal layout
Wiring method
Remove about 6mm of the cable insulation. Wire the stripped cable after twisting it to prevent
it from becoming loose. In addition, do not solder it.
Loosen the terminal screw and insert the cable into the terminal.
Tab. 3-10: Connection to the terminals
CAUTION:
E
Tighten the cable fixing screws within the specified torque range. Undertightening can
cause cable disconnection or malfunction. Overtightening can cause a short circuit
or malfunction due to damage to the screw or unit.
FR-F700 EC
6mm
Item
Description
Screw size
M3
Tightening torque
0.5Nm–0.6Nm
Cable size
0.3mm²–0.75mm²
Flat blade screw driver
Screwdriver
Edge thickness: 0.4mm × 2.5mm
Control circuit specifications
Fig. 3-9:
Preparation of the cable
I001018E
I001326E
3 - 21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-f746 ec

Table of Contents