Parameter
Current monitoring reference (Pr. 56)
Set the current to be referenced when the current monitor (inverter output current, etc.) is se-
lected for the terminal CA and terminal AM display.
● Set the current value when the current output at terminal CA is 20mA DC. The analog current
output and current value at terminal CA are proportional. (The maximum output current is
20mA DC.)
● Set the current value when the voltage output at terminal AM is 10V DC. The analog voltage
output and current value at terminal AM are proportional. (The maximum output voltage is
10V DC.)
10V DC/
20mA DC
Terminal AM response adjustment (Pr. 867)
Using Pr. 867, the output voltage response of the terminal AM can be adjusted within the range
0 to 5s.
Increasing the setting stabilizes the terminal AM output more but reduces the response level.
(Setting "0" sets the response level to 7ms.)
Adjustment of response level of terminal CA (Pr. 869)
The response level of the output current of the terminal CA can be adjusted between 0 and 5s
with Pr. 869.
Increasing the setting stabilizes the terminal CA output more but reduces the response level.
(Setting "0" sets the response level to about 7ms.)
FR-F700 EC
500A
Rated output current
(3600A)
(initial value)
Setting range of Pr. 56
Monitor display and monitor output signals
Fig. 6-82:
Current monitoring reference
I001165E
6 - 147