Parameter
Specifications
● Communication specifications
(conforming to BACnet standard of physical medium EIA-485)
Item
Physical medium
Network topology
Communication method
Communication protocol
Maximum connection
Node number
Supported property of BACnet standard
object type
Supported BIBBs
BACnet standard device profile
Segmentation
Device address binding
Tab. 6-96:
Token Passing (TP)
BACnet Interoperability Building Block
NOTES
This product conforms to BACnet Application Specific Controller (B-ASC).
This product is designed for multiple master network, therefore 2-wire type connection is
supported.
● Node with network bias resistors
This product is a node with local bias resistors. Therefore at least one node must be a node with
network bias resistors in the network configuration.
When configuring the network with only this products, refer to the following figure, and make the
node with network bias resistors. (When using two sets in one segment, insert them into both
end of the network.)
FR-F700 EC
Connection port
Data transfer method
Baud rate
Start bit
Data length
Parity bit
Stop bit
Master
BACnet communication specifications
Communication operation and setting
Description
EIA-485 (RS485)
RS485 terminal (PU connector is not available)
NRZ encoding
9600 bps, 19200 bps, 38400 bps, 76800 bps
Fixed to 1Bit
Fixed to 8Bit
Fixed to none
Fixed to 1Bit
Bus topology
Token passing
(token bus)
Master-slave (only the master is available for this product)
MS/TP (master-slave/token passing LAN)
255 (up to 32 for one segment, addition with a repeater is available)
0 to 127
0 to 127 (this product is the master)
refer to page 6-315
refer to page 6-326
refer to page 6-326
Not supported
Not supported
6 - 311