Parameter
How to find the set frequency for override:
Set frequency [Hz]
Main speed set frequency [Hz]: Terminal 1, 4 or multi-speed setting
Compensation amount [%]: Terminal 2 input
Example
Pr. 73 = 5
The set frequency changes as shown below according to the terminal 1 (main speed) and
terminal 2 (auxiliary) inputs.
Fig. 6-119: Set frequency in dependence on the terminal 1 and terminal 2 signals
NOTES
When the Pr. 73 setting was changed, check the voltage/current input switch setting. Differ-
ent setting may cause a fault, failure or malfunction. (Refer to page 6-188 for setting.)
The AU signal must be turned on to use the terminal 4.
When inputting compensation to multi-speed operation or remote setting, set "1" (compen-
sation made) to Pr. 28 "Multi-speed input compensation selection". (Initial value is "0".)
FR-F700 EC
=
Main speed set frequency [Hz]
Initial value
(50% to 150%)
Voltage across terminals 2-5
75
50
37,5
25
12,5
0
Frequency setting by analog input (terminals 1, 2 and 4)
×
Fig. 6-118:
Override
0
2,5
Terminal 1 input voltage [V]
Compensation amount [%]
--------------------------------------------------------------------- -
100 [%]
Terminal 2: 5V DC
(150%)
Terminal 2: 2.5V DC
(100%)
Terminal 2: 0V DC
(50%)
5
I001189E
I001190E
6 - 197