Mitsubishi Electric FR-F740 EC Instruction Manual page 222

Fr-f700 series
Table of Contents

Advertisement

Frequency setting by external terminals
When Pr. 59 is set to any of "1 to 3, 11 to 13" (remote setting function valid), the functions of the
RH, RM and RL signals are changed: RH ⇒ acceleration, RM ⇒ deceleration and RL ⇒ clear.
Acceleration RH
Deceleration RM
Forward rotation STF
Fig. 6-26:
Remote setting function
External operation:
PU operation:
By setting Pr. 59 = "11 to 13", the speed can be decelerated to the frequency lower than the main
speed (set by the external operation frequency (except multi-speed setting) or PU operation
frequency).
Forward rotation (STF)
Fig. 6-27:
6 - 72
ON
Clear RL
Power supply
* External operation frequency (other than multi-speed) or PU running frequency.
Example of the remote setting function (1)
Frequency set by RH/RM operation + external running frequen-
cy or PU running frequency (other than multi-speed).
(PU operation frequency when Pr. 79 = "3" (external, PU com-
bined)) and terminal 4 input
(When making analog input compensation, set "1" to Pr. 28 "Multi-
speed input compensation selection".
When Pr. 28 is set to "0" and acceleration/deceleration is made to
reach the set frequency of the analog voltage input (terminal 2 or
terminal 4) by RH/RM, the auxiliary input by terminal 1 becomes
invalid.)
Frequency set by RH/RM operation + PU running frequency
Main speed
Minimum frequency
0
Acceleration RH
Deceleration RM
Example of the remote setting function (2)
ON
ON
ON
ON
ON
ON
ON
ON
ON
Pr. 59 = 1, 2
Pr. 59
Pr. 59 = 3
= 2, 3
ON
ON
Pr. 59 = 1, 2, 3
Decelerates to the main speed
Pr. 59 = 11, 12, 13
Decelerates to the minimum frequency
Time
Parameter
Pr. 59 = 1
Time
ON
ON
I001133E
I002092E

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-f746 ec

Table of Contents