Installation
2.4.2

Inverter placement

Clearances around the inverter
Always observe the specified minimum clearances to ensure good heat dissipation and ade-
quate accessibility of the frequency inverter for servicing.
Ambient temperature and humidity
5cm
Measurement
position
LD/SLD
150 % −10 to +50 −10 to +40
120 % −10 to +40 −10 to +30
Initial setting
Leave enough clearances and take
cooling measures.
Fig. 2-10: Clearances
NOTES
For replacing the cooling fan of the 04320 or more, 30cm of space is necessary in front of
the inverter. Refer to section 8.1.7 for fan replacement.
Since the fan cover of the inverter FR-F746 is fixed with screws, leave enough clearances
so that the screws can be removed with a driver and such.
It is not necessary to leave spaces on both sides of the inverter FR-F746.
Inverter mounting orientation
Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.
Above the inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed
above the inverter should be heat resistant.
NOTE
The ambient temperature should be 50°C or less for the inverter FR-F740 and 40°C or less
for the inverter FR-F746 at a distance of 5cm from the centre bottom of the inverter.
FR-F700 EC
Clearances (side)
Measurement
position
5cm
5cm
≥ 5cm
Temperature [°C]
Ambient
humidity:
FR-F740 FR-F746
90%
1cm or more for 00083 or less
01160 or less
01800 or more
≥ 10cm
≥ 5cm
≥ 10cm
≥ 10cm
Enclosure design
Clearances (front)
≥ 20cm
≥ 10cm
≥ 5cm
≥ 20cm
1cm or more for 00083 or less
I001005E
2 - 11