Function assignment of external terminals
6.9.5

Output terminal function selection (Pr. 190 to Pr. 196)

You can change the functions of the open collector output terminal and relay output terminal.
Pr.
Name
No.
RUN terminal
190
function selection
SU terminal
191
function selection
Open
IPF terminal
collector
192
function selection
output
terminal
OL terminal
193
function selection
FU terminal
194
function selection
ABC1 terminal
195
function selection
Relay
output
ABC2 terminal
196
terminal
function selection
The above parameter can be set when Pr. 160 = 0.
You can set the functions of the output terminals.
Refer to the following table and set the parameters:
0–99: Source logic
100–199: Sink logic
Setting
Terminal Function
Source
Sink
Logic
Logic
0
100
RUN
1
101
SU
2
102
IPF
3
103
OL
4
104
FU
5
105
FU2
7
107
RBP
Tab. 6-20:
Output terminal function assignment (1)
6 - 120
Initial
Initial Signal
Value
0
RUN (inverter running)
1
SU (up to frequency)
IPF (instantaneous power
2
failure, under voltage)
3
OL (overload alarm)
FU (output frequency
4
detection)
99
ALM (alarm output)
9999
No function
Inverter running
Up to frequency
Instantaneous power failure/
under voltage
Overload alarm
Output frequency detection
Second output
frequency detection
Regenerative brake prealarm
Setting Range
Parameters referred to
0–5/7/8/10–19/25/
26/45–54/64/67/
70–79/82/85/90–96/
98/99/100–105/107/
108/110–116/ 125/
126/145–154/164/
167/170/179/182/
185190–196/
198/199/9999
0–5/7/8/10–19/25/
26/45–54/64/67/
70–79/82/85/90/91/
94–96/98/99/
100–105/107/108/
110–116/125/126/
145–154/164/167/
170/179/182/185
190/191/194–196/
198/199/9999
Operation
Output during operation when
the inverter output frequency
rises to or above Pr. 13
"Starting frequency".
Output when the output fre-
quency is reached to the set
frequency.
Output at occurrence of an
instantaneous power failure
or when undervoltage protec-
tion is activated.
Output while stall prevention
function is activated.
Output when the output
frequency reaches the
frequency setting in Pr. 42
(Pr. 43 for reverse rotation).
Output when the output fre-
quency reaches the fre-
quency setting in Pr. 50.
Output when 85% of the
regenerative brake duty set in
Pr. 70 is reached.
Setting can be made for the
01800 or more.
Parameter
Refer to
Section
13
Starting
6.6.2
frequency
76
Alarm code
6.12.2
output selection
Related
Refer to
Parameters
Page
6-125
Pr. 41
6-127
Pr. 57
6-153
Pr. 22, Pr. 23,
Pr. 66, Pr. 148,
6-44
Pr. 149, Pr. 154
Pr. 42, Pr. 43
6-127
Pr. 50
6-127
Pr. 70