Misoperation prevention and parameter setting restriction
Restarting method when stop was made by pressing the STOP key from the PU during
external operation ("PS" is displayed)
Operation panel FR-DU07
After the motor has decelerated to a stop, turn off the STF or STR signal.
Push the PU/EXT key to release PS:
– three times (when Pr. 79 = "0 (initial value) or 6")
– once (when Pr. 79 = "2, 3, or 7").
"PS" is displayed.
Turn on the STF or STR signal.
Parameter unit FR-PU04/FR-PU07
After the motor has decelerated to a stop, turn off the STF or STR signal.
Press the EXT key. The message "PS" is canceled.
Turn on the STF or STR signal.
The motor can be restarted by making a reset using a power supply reset or RES signal.
Operation panel
Fig. 6-132: Stop during external operation
NOTE
If Pr. 250 "Stop selection" is set to other than "9999" to select coasting to a stop, the motor
will not be coasted to a stop but decelerated to a stop by the PU stop function during exter-
nal operation.
To restart after the inverter is stopped by PU with PLC function, reset using a power supply
reset or the RES signal (sending stop signal from GX Developer, can also perform the
reset.)
WARNING:
P
Do not reset the inverter with the start signal on. Doing so will cause the inverter to
start immediately after a reset, leading to hazardous conditions.