Mitsubishi Electric FR-F740 EC Instruction Manual page 272

Fr-f700 series
Table of Contents

Advertisement

Function assignment of external terminals
Setting
Terminal Function
Source
Sink
Logic
Logic
49
149
Y49
50
150
Y50
51
151
Y51
52
152
Y52
53
153
Y53
54
154
Y54
64
164
Y64
67
167
Y67
70
170
SLEEP
71
R01
72
R02
73
R03
74
R04
75
RI01
76
RI02
77
RI03
78
RI04
79
179
Y79
82
182
Y82
85
185
Y85
90
190
Y90
91
191
Y91
92
192
Y92
Tab. 6-20:
Output terminal function assignment (3)
6 - 122
During pre-charge operation
During second pre-charge
operation
Pre-charge time over
Second pre-charge time over
Pre-charge level over
Second pre-charge level over
During retry
During power failure
PID output interruption
Commercial-power supply side
motor 1 connection RO1
Commercial-power supply side
motor 2 connection RO2
Commercial-power supply side
motor 3 connection RO3
Commercial-power supply side
motor 4 connection RO4
Inverter side motor 1 connection
RIO1
Inverter side motor 2 connection
RIO2
Inverter side motor 3 connection
RIO3
Inverter side motor 4 connection
RIO4
Pulse train output of output
power
BACnet binary output
DC feeding
Life alarm
Alarm output 3 (power-off signal)
Energy saving average value
updated timing
Operation
Output during the pre-charge
operation.
Output when the pre-charged
time exceeds the time set in
Pr.764 or Pr.769.
Output when the pre-charged
amount exceeds the set level
in Pr. 763 or Pr. 768.
Output during retry
processing.
Output during output shutoff
due to power failure or under
voltage.
Output when the PID output
interruption function is
executed.
Used when using advanced
PID control (pump function).
Output in pulses every time
the accumulated output
power of the inverter reaches
the Pr. 799 setting.
Control of binary output from
BACnet is available.
Output during power failure or
under voltage of AC power.
Output when any of the con-
trol circuit capacitor, main cir-
cuit capacitor and inrush
current limit circuit or the
cooling fan approaches the
end of its service life.
Output when an error occurs
due to the circuit failure or
connection alarm of the
inverter.
Turned on and off alternately
every time the power saving
average value is updated
when the power saving moni-
tor is used.
Parameter
Related
Refer to
Parameters
Page
Pr. 127–Pr. 134,
Pr. 241, Pr. 553,
6-328
Pr. 554,
6-350
Pr. 575–Pr. 577,
6-358
Pr. 753–Pr. 769,
C42–C45
Pr. 65–Pr. 69
6-169
Pr. 57
6-153
Pr. 127–Pr. 134,
6-328
Pr. 575–Pr. 577
Pr. 575–Pr. 591
6-361
Pr. 799
6-135
6-310
Pr. 30, Pr. 70
6-97
Pr. 255–Pr. 259
6-390
6-126
Pr. 52, Pr. 54,
Pr. 158,
6-178
Pr. 891–Pr. 899

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-f746 ec

Table of Contents