Parameter
● Alarm history
Register
40501
40502
40503
40504
40505
40506
40507
40508
Tab. 6-109: Alarm history
Data
H00
H10
H11
H12
H20
H21
H22
H30
H31
H40
H50
H51
H52
H60
H70
H80
Tab. 6-110: Alarm code list
* Refer to the FR-F700 PLC function programming manual for details.
● Model information monitor
Register
44001–44010
44011–44013
Tab. 6-111: Inverter type monitor
FR-F700 EC
Definition
Read/write
Alarm history 1
Read/write
Alarm history 2
Read
Alarm history 3
Read
Alarm history 4
Read
Alarm history 5
Read
Alarm history 6
Read
Alarm history 7
Read
Alarm history 8
Read
Description
Data
No alarm
H81
E.OC1
H90
E.OC2
H91
E.OC3
HA0
E.OV1
HA1
E.OV2
HA2
E.OV3
HA4
E.THT
HA5
E.THM
HA6
E.FIN
HA7
E.IPF
HA8
E.UVT
HB0
E.ILF
HB1
E.OLT
HB2
E.BE
HB3
E.GF
HC0
Definition
Read/write
Inverter type
Read/write
Capacity
Read
Communication operation and setting
Remarks
Being 2 bytes in length, the data is stored as
"H00
". The error code can be referred to in the
low-order 1 byte.
Performing write using the register 40501 batch-
clears the alarm history. Set any value as data.
Description
Data
E.LF
HC1
E.OHT
HC2
E.PTC
HC4
E.OPT
HC5
E.OP1
HC6
E.OP2
HC7
E.16 *
HE4
E.17 *
HE5
E.18 *
HE6
E.19 *
HF1
E.20 *
HF2
E.PE
HF5
E.PUE
HF6
E.RET
HF7
E.PE2
HFD
E.CPU
Remarks
Reading inverter type in ASCII code.
"H20" (blank code) is set for blank area
Example of FR-F740-EC:
H46, H52, H2D, H46, H37, H34, H30, H2D, H45,
H43, H20.....H20
Reading inverter capacity in ASCII code.
Data is read in increments of 0.1kW, and rounds
down to 0.01kW increments
"H20" (blank code) is set for blank area
Example:
0.75K . . . . "-----7" (H20, H20, H20, H20,
H20, H37)
Description
E.CTE
E.P24
E.CDO
E.IOH
E.SER
E.AIE
E.LCI
E.PCH
E.PID
E.1
E.2
E.5
E.6
E.7
E.13
6 - 325