Parameter
I/O signals and parameter setting
Turn on the X14 signal to perform PID control. When this signal is off, PID action is not performed
and normal inverter operation is performed. (When Pr. 128 = "10, 11, 20, 21, 40 or 41".)
Enter the set point across inverter terminals 2-5 or into Pr. 133 and enter the measured value
signal across inverter terminals 4-5. At this time, set "20, 21, 120 or 121" in Pr. 128.
When entering the calculated deviation signal of an external (PID) controller, enter it across ter-
minals 1-5. At this time, set "10, 11, 110, 111" in Pr. 128.
Signal
X14
X64
X72
X77
X78
PU
Commu-
nication
Tab. 6-113: I/O signals and parameter settings (1)
FR-F700 EC
Terminal
Function
used
PID control
selection
PID forward/
reverse action
switchover
PID integral
value reset
Pre-charge
end command
Second pre-
charge end
command
2
2
Set point input
Set point input
Deviation
1
1
signal input
Measured
4
4
value input
Deviation
value input
Set point input Input the set point from
Set point,
measured
value input
Description
Turn ON X14 to perform PID
control.
By turning ON X64, forward action
can be selected for PID reverse
action (Pr. 128 = 10, 20, 110, 120),
and reverse action for forward
action (Pr. 128 = 11, 21, 111, 121).
ON:
Integral and differential
values are reset
OFF: Normal processing
Turn ON X77 to end the pre-
charge operation and start PID
control.
Turn ON X78 while RT is ON to
end the pre-charge operation and
start PID control.
Enter the set point for PID control. Pr. 128 = 20, 21, 120, 121
0–5V................ 0–100%
0–10V.............. 0–100%
0/4–20mA........ 0–100%
Set the set value (Pr. 133) from
the operation panel or parameter
unit.
Input the deviation signal
calculated externally.
−5V–+5V............... −100%–+100%
−10V–+10V .......... −100%–+100%
Input the signal from the detector
(measured value signal).
0/4–20mA........ 0–100%
0–5V................ 0–100%
0–10V.............. 0–100%
Input the deviation value from
LONWORKS, CC-Link
communication or BACnet
communication.
LONWORKS, CC-Link
communication or BACnet
communication
Input the set point and measured
value from LONWORKS, CC-Link
communication or BACnet
communication
PID control
Parameter Setting
Set "14" to any of
Pr. 178 to Pr. 189.
Set "64" to any of
Pr. 178 to Pr. 189.
Set "72" to any of
Pr. 178 to Pr. 189.
Set "77" to any of
Pr. 178 to Pr. 189.
Set "78" to any of
Pr. 178 to Pr. 189.
Pr. 133 = 9999
Pr. 73 = 1
, 3, 5, 11, 13, 15
Pr. 73 = 0, 2, 4, 10, 12, 14
Pr. 73 = 6, 7, 16, 17
Pr. 128 = 20, 21, 120, 121
Pr. 133 = 0–100%
Pr. 128 = 10
, 11, 110, 111
Pr. 73 = 2, 3, 5, 7, 12, 13,
15, 17
Pr. 73 = 0, 1
, 4, 6, 10, 11,
14, 16
Pr. 128 = 20, 21, 40, 41, 120,
121, 140, 141
Pr. 267 = 0
Pr. 267 = 1
Pr. 267 = 2
Pr. 128 = 50, 51
Pr. 128 = 40, 41, 140, 141
Pr. 128 = 60, 61
6 - 335