Complete Hardware Guide for EX8208 Ethernet Switches

Cabinet Requirements and Specifications for an EX8208 Switch

Table 41: Cabinet Requirements and Specifications for an EX8208 Switch

Cabinet Requirement
Cabinet size and clearance
94
You can mount an EX8208 switch on a cabinet that contains a 19-in. rack as defined in
Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D)
published by the Electronics Industry Association (
Cabinet requirements consist of:
Cabinet size and clearance
Cabinet airflow requirements
Table 41 on page 94 summarizes cabinet requirements and specifications for EX8208
switches.
http://www.eia.org
Guidelines for the EX8208 Switch
The minimum cabinet size for accommodating an EX8208
switch is 23.62 in. (60 cm) wide and 30.0 in. (76.2 cm) deep.
Large cabinets improve airflow and reduce the chance of
overheating. To accommodate a single EX8208 switch in
a four-post rack, the cabinet must be at least 14 U high (or
15 U if you install the power cord tray, which is optional for
the four-post rack). To accommodate a single EX8208
switch in a two-post rack, the cabinet must be at least 15
U high.
A U is the standard rack unit defined in Cabinets, Racks,
Panels, and Associated Equipment (document number
EIA-310–D) published by the Electronics Industry
http://www.eia.org
Association (
With adequate cooling air and airflow clearance, you can
stack three EX8208 switches in a cabinet with a four-post
rack that has at least 42 U of usable vertical space. (45 U
are required if you install the optional power cord tray.) You
can stack three EX8208 switches in a cabinet with a
two-post rack that has at least 45 U of usable vertical space
(for two-post rack installations, installing the power cord
tray is mandatory). In all cases, the rack must meet the
strength requirements to support the weight.
The minimum total clearance inside the cabinet is 29.2 in.
(74.17 cm) between the inside of the front door and the
inside of the rear door.