Mx10003 Router Cabinet Requirements And Specifications - Juniper MX10003 Hardware Manual

Universal routing platform
Hide thumbs Also See for MX10003:
Table of Contents

Advertisement

MX10003 Router Cabinet Requirements and Specifications

Table 25 on page 68
summarizes cabinet requirements and specifications for MX10003 router.
Table 25: Cabinet Requirements and Specifications for an MX10003 Router
Cabinet Requirement
Cabinet size and clearance
Guidelines for the MX10003 Router
The minimum-sized cabinet that can accommodate the router is 19-in. (482-mm)
wide, and 30.0-in. (762-mm) deep. A cabinet larger than the minimum
requirement provides better airflow and reduces the chance of overheating. If
you provide adequate cooling air and airflow clearance, you can stack several
routers in a cabinet that has sufficient usable vertical space. Each router requires
3 U.
A U is the standard rack unit defined in Cabinets, Racks, Panels, and Associated
Equipment (document number EIA-310-D) published by the Electronic
Components Industry Association (ECIA) (http://www.ecianow.org).
With adequate cooling air and airflow clearance, you can stack multiple
MX10003 routers in a cabinet with a four-post rack. In all cases, the rack must
meet the strength requirements to support the weight.
The minimum total clearance inside the cabinet is 30.7 in. (780 mm) between
the inside of the front door and the inside of the rear door.
68