Connecting Earth Ground To An Ex8208 Switch - Juniper EX8208 Complete Hardware Manual

Juniper networks switch user manual
Hide thumbs Also See for EX8208:
Table of Contents

Advertisement

Connecting Earth Ground to an EX8208 Switch

Copyright © 2010, Juniper Networks, Inc.
Washers and 10-32x.25-in. screws to secure the grounding lug to the protective earthing
terminal
Phillips (+) screwdriver, number 2
To connect earth ground to an EX4500 switch:
Connect one end of the grounding cable to a proper earth ground, such as the rack in
1.
which the switch is mounted.
Place the grounding lug attached to the grounding cable over the protective earthing
2.
terminal. See Figure 64 on page 163.
NOTE: If you mounted the switch on four posts of a rack using the
four-post rack-mount kit, the protective earthing terminal on the switch
is accessible through the slot on the left rear bracket.
The protective earthing terminal on the switch mounted on four posts is
available only if the rack is 27.5 in. deep through 30.5 in. deep for a switch
mounted flush with the rack front and 29.5 in. deep through 32.5 in. deep
for a switch mounted 2 in. recessed from the rack front.
Secure the grounding lug to the protective earthing terminal with screws.
3.
Dress the grounding cable and ensure that it does not touch or block access to other
4.
switch components and that it does not drape where people could trip over it.
The protective earthing terminal is located on the left side of the chassis in an EX8208
switch.
An AC-powered EX Series switch chassis gets additional grounding when you plug the
power supply in the switch into a grounded AC power outlet by using an AC power cord
appropriate for your geographical location. See "AC Power Cord Specifications for an
EX8200 Switch" on page 106.
Ensure that you have the following parts and tools available:
Grounding cable for your EX8208 switch—The grounding cable must be 6 AWG
(13.3 mm²), minimum 60°C wire, or as permitted by the local code.
Grounding lug for your grounding cable. See "Grounding Cable and Lug Specifications
for EX8200 Switches" on page 80.
Washers and ¼-20x.75-in. screws to secure the grounding lug to the protective earthing
terminal
Phillips (+) screwdriver, number 2
To connect earth ground to an EX8208 switch:
Chapter 10: Connecting the Switch
167

Advertisement

Table of Contents
loading

Table of Contents