1-8
Installing Your Ultra1500
Allow 30.0 mm (1.18 in.)
from adjacent wall
Publication 2092-UM001D-EN-P — July 2005

Ventilation Requirements

This section provides information to assist you in sizing your cabinet and
locating your Ultra1500 drive(s) inside the cabinet.
Figure 1.2
Minimum Clearance Requirements
50.0 mm (1.97 in.) clearance
for airflow and installation
Ultra1500s mounted
vertically on the panel
Allow 10.0 mm (0.39 in.)
between drives
50.0 mm (1.97 in.) clearance
for airflow and installation
If the cabinet is ventilated, use filtered or conditioned air to
IMPORTANT
prevent the accumulation of dust and dirt on electronic
components. The air should be free of oil, corrosives, or
electrically conductive contaminates.
Refer to Appendix A for Ultra1500 power dissipation specifications.
Do not mount drive on its side.
Minimum cabinet depth:
2092-DA1, -DA2, and -DA3 = 216 mm (8.52 in.)
2092-DA4, and -DA5 = 261 mm (10.28 in.)