User-Definable Alarms; Introduction - ADTRAN MX2820 System Manual

Adtran mx2820 multiplexer: system manual
Hide thumbs Also See for MX2820:
Table of Contents

Advertisement

User-Definable Alarms

INTRODUCTION

This subsection provides the instructions to assist the user in defining alarm parameters for
environmental alarms managed by the MX2820 System Controller Unit (SCU).
The user-definable environmental alarms include the following:
• AUX #1 Input
• AUX #2 Input
• AUX #3A Input
• AUX #3B Input
• PWR Bus A Input
• PWR Bus B Input
The auxiliary alarm parameters include the following:
• Alarm description (Defaults are Aux #1 Input, Aux #2 Input, Aux #3A Input, and Aux#3B
Input)
• Alarm severity level (Default is MAJOR)
• Access Identifier (AID) index (Defaults are 1=Aux1; 2=Aux2; 3=Aux3A or 3B)
• Alarm condition code (Defaults are AUX1, AUX2, AUX3A, AUX3B)
The alarm parameters for the power supplies include:
• Alarm severity level for power supply failure (Default is MAJOR)
• AID index (Defaults are 4=PWRA; 5=PWRB)
• Alarm condition code (Default is PWRA and PWRB)
This document also provides the instructions that allow the user to set the alarm severity level
for a module that is removed from the MX2820 shelf.
The alarm severity levels include the following:
• INFO
• ALERT
• MINOR: Non Service Affecting (NSA) Module Removed Level
• MAJOR: Service Affecting (SA) Module Removed Level (default)
• CRITICAL
61186003L1-1D
UIG-570
5-149