Omron SYSMAC CJ - REFERENCE MANUAL 01-2008 Reference Manual page 1107

Sysmac cs/cj/one nsj series programmable controllers
Table of Contents

Advertisement

Network Instructions
Operands
1068
S: First word of send message
Specifies the first word of the send message (S to S+272 max.).
15
S
15
12
S+1
0
15
12
S+2
0
15
12
S+3
0
15
12
S+4
0
15
12
S+5
0
15
S+6
to
S+272
When there is Service Data (data other than the
Attribute ID), the byte-order of this data is specified in
bits 12 to 15 of C+1. Up to 534 bytes (267 words) can
be set.
0
Set the number of bytes of source data from words S+1 on. For
example, set S to 000A hex if there are 5 words of data (S+1 to
S+5). Do not include the 2 bytes in word S itself. Include the
leftmost bytes of S+1 to S+5, which contain 00.
Also, include the number of bytes of Service Data starting at S+6.
(If the first or last word contains just one byte of data, do not count
the empty byte in that word.)
11
8
7
0
0
Destination Node Address
(00 to max. node address (hex))
11
8
7
0
0
Service Code (hex)
11
8
7
0
0
Class ID (hex)
11
8
7
0
0
Instance ID (hex)
11
8
7
0
0
Attribute ID (hex)
If the Attribute ID is not used, set it to FFFF hex.
(The Attribute ID cannot be set to 0000 hex.)
0
Service Data
Section 3-25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents