Setting the Set Point (SP)

Initial Setting Level
Input Type
in-t
5
Operation Level
PV/SP
C
25.0
100.0
Auxiliary Output
Opening or Closing in
Alarm
3-6

Setting the Set Point (SP)

Operation Level
C
20.0
0.0
Operation Level
C
20.0
0.0
50.0
3-6-1

Changing the SP

56
14. Press the O Key for at least one second to move from the advanced
function setting level to the initial setting level.
15. Press the O Key for at least one second to move from the initial setting
level to the operation level.
• When "close in alarm" is set, the status of the auxiliary output is output
unchanged. When "open in alarm" is set, the status of the auxiliary output
function is reversed before being output.
• Each auxiliary output can be set independently.
• These settings are made in the Auxiliary Output 1 to 3 Open in Alarm
parameters (advanced function setting level).
• The default is n-o: Close in Alarm.
• When "open in alarm" is set for the alarm 1 output, the open in alarm sta-
tus is also applied to heater burnout, HS alarm, heater overcurrent, and
input error outputs.
Auxiliary output
functions 1 to 3
Close in Alarm ON
OFF
Open in Alarm
ON
OFF
• The alarm output will turn OFF (i.e., the relay contacts will open) when
power is interrupted and for about two seconds after the power is turned
ON regardless of the setting of the Auxiliary Output 1 to 3 Open in Alarm
parameter.
The operation level is displayed when the power is turned ON. The process
value (PV) is at the top of the display, and the set point (SP) is at the bottom.
For Controllers that support a No. 3 display (E5AN/E5EN-H), the contents
set in the PV/SP Display Screen Selection parameter (advanced function
setting level) are displayed below the PV and SP.
The MV is displayed as the default. For details, refer to 3-11 Setting the No.
3 Display.
• The set point cannot be changed when the Operation/Adjustment Protect
parameter is set to 3. For details, refer to 4-9 Using the Key Protect Level.
Section 3-6
Auxiliary
Indicators
output
(SUB1 to SUB3)
ON
Lit
OFF
Not lit
OFF
Lit
ON
Not lit