Adjustment Level
See
See
lcr1
Leakage Current 1 Monitor
Function
Monitor
See
See
hs1
HS Alarm 1
Function
Setting
■ Related Parameters
Heater current 2 value monitor (adjustment level): Page 182
Heater overcurrent use, Heater overcurrent latch, Heater overcurrent hystere-
sis (advanced function setting level): Page 272, 273
This parameter measures the heater current from the CT input used for
detecting SSR short-circuits.
This parameter measures and displays the heater current when the heater is
OFF.
• HS alarms are not detected if the control output (heating) OFF time is
100 ms or less.
Monitor range
0.0 to 55.0
• ffff is displayed when 55.0 A is exceeded.
• If an HS alarm 1 alarm is output, the HA indicator will light and the No. 1
display for the leakage current 1 monitor will flash.
■ Related Parameters
HS alarm 1, HS alarm 2 (adjustment level): Page 197
HS alarm use (advanced function setting level): Page 257
Error displays lcr1: Page 306
This parameter sets the current for the HS alarm to be output.
• An HS alarm is output when the leakage current value exceeds the set-
ting of this parameter.
• When the set value is 50.0, the HS alarm output is turned OFF. When the
set value is 0.0, the HS alarm output is turned ON.
Setting range
0.0 to 50.0
A
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
Alarm 1 must be assigned.
The HS Alarm parameter must be
set to ON.
Unit
A
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
Alarm 1 must be assigned.
The HS Alarm parameter must be
set to ON.
Unit
Default
50.0
Section 5-4
197