Setting Level Configuration and Key Operations
Monitor/Setting Item Level
Manual Control Level
Initial Setting Level
Advanced Function
Setting Level
Communications Setting
Level
Calibration Level
• To switch to the monitor/setting item level, press the PF Key from the
operation level, adjustment level, bank setting level, or PID setting level.
The contents set for monitor/setting items 1 to 5 can be displayed. You
can move from the monitor/setting item level to the operation level or initial
setting level. (E5AN/EN-H only.)
• When the O Key is pressed for at least 3 seconds from the operation
level's auto/manual switching display, the manual control level will be dis-
played. (The MANU indicator will light.)
• When the PF Setting is set to A-M (auto/manual) and the PF Key is
pressed for more than one second from the operation level, adjustment
level, bank setting level, or PID setting level the manual control level will
be displayed. (E5AN/EN-H only.)
• This is the level for changing the MV in manual mode.
• To return to the operation level, press the O Key for at least one second.
It is also possible to return to the operation level by pressing the PF Key
for more than one second when the PF Setting is set to A-M.
• To move to the initial setting level from the operation level, the adjustment
level, bank setting level, PID setting level, or monitor/setting item level,
press the O Key for at least 3 seconds. The PV display flashes after one
second. This level is for specifying the input type and selecting the control
method, control period, setting direct/reverse operation, setting the alarm
types, etc. You can move to the advanced function setting level or commu-
nications setting level from this level. To return to the operation level,
press the O Key for at least one second. To move to the communications
setting level, press the O Key for less than one second.
(When moving from the initial setting level to the operation level, all the
indicators will light.)
Note Pressing the O Key for at least 3 seconds in the operation level's
auto/manual switching display will move to the manual control level,
and not the initial setting level.
• To move to the advanced function setting level, set the Initial Setting/Com-
munications Protect parameter in the protect level to 0 (the default) and
then, in the initial setting level, input the password (−169).
• From the advanced function setting level, it is possible to move to the cali-
bration level or to the initial setting level.
• This level is for setting the automatic display return time and standby
sequence, and it is the level for moving to the user calibration and other
functions.
• To move to the communications setting level from the initial setting level,
press the O Key once (for less than 1 s). When using the communica-
tions function, set the communications conditions in this level. Communi-
cating with a personal computer (host computer) allows set points to be
read and written, and manipulated variables (MV) to be monitored.
• To move to the calibration level, input the password (1201) from the
advanced function setting level. The calibration level is for offsetting error
in the input circuit.
• You cannot move to other levels from the calibration level by operating the
keys on the front panel. To cancel this level, turn the power OFF then back
ON again.