Advanced Function Setting Level
pvdp
PV Decimal Point Display
Function
Setting
See
See
pvst
PV Status Display Function
Monitor
See
See
276
The display below the decimal point in the PV can be hidden for temperature
inputs.
• The PV decimals below the decimal point can be hidden by setting the PV
Decimal Point Display parameter to OFF. When this parameter is set to
ON, the display below the decimal point will appear according to the input
type setting.
Setting range
on: ON, off: OFF
■ Related Parameters
Input type (initial setting level): Page 224
• The PV in the No. 1 display for the PV/SP, PV, or PV/Manual MV (Valve
Opening) Screen is alternately displayed in 0.5-s cycles with the control
and alarm status specified for the PV status display function.
off: No PV status display
manu: MANU is alternately displayed during manual control.
stop: STOP is alternately displayed while operation is stopped.
alm1: ALM1 is alternately displayed during Alarm 1 status.
alm2: ALM2 is alternately displayed during Alarm 2 status.
alm3: ALM3 is alternately displayed during Alarm 3 status.
alm: ALM is alternately displayed when Alarm 1, 2, or 3 is set to ON.
ha: HA is alternately displayed when a heater burnout alarm, HS alarm,
or heater overcurrent alarm is ON.
■ Related Parameters
Process value/set point, PV (operation level): Page 177
PV/MV (manual MV) (manual control level): Page 221
The input type must be set to tem-
perature input.
ON
Monitor range
Section 5-10
Default
Default
off