Protect Level
The time taken to move to the protect level
can be adjusted by changing the "Move to
protect level time" setting.
Move to Protect Level:
pmov
Displayed only when a password
is set. Restricts moving to protect
0
level.
M
Operation/Adjustment Pro-
tect:
oapt
Restricts displaying and
modifying menus in opera-
0
tion, adjustment, and man-
ual control levels.
M
Initial Setting/
Communications Protect:
icpt
This protect level restricts move-
0
ment to the initial setting, com-
munications setting, and ad-
M
vanced function setting levels.
Setting Change Protect:
wtpt
Protects changes to setups
by operating the front panel
off
keys.
M
pfpt
PF Key Protect
Restricts PF key operation
off
(E5AN/EN-H only)
M
Parameter Mask Enable:
pmsk
Displayed only when a
parameter mask is set.
on
M
Password to Move to
prlp
Protect Level:
0
Password setting
M
340
Press the O Key for at least 1 s.
Press the O Key for at least 3 s.
Other than the Auto/Manual Switch display
Press the O Key less than 1 s.
Communications
Setting Level
Displayed only for models with communications. Changes
are effective after cycling power or after a software reset.
Protocol Setting:
psel
Switches between
CompoWay/F (SYS-
cwf
WAY) and Modbus.
M
u-no
Communications Unit No.
1
M
Communications
bps
Baud Rate
9.6
CompoWay/F
(SYSWAY) only
M
Communications
len
Data Length
7
M
sbit
Communications
Stop Bits
2
M
prty
Communications Parity
even
M
Send Data Wait Time
sdwt
20
M
Initial Setting Level
Press the O Key less than 1 s.
in-t
Input Type
5
alt2
M
in-h
Scaling Upper Limit
100
alh2
c
M
in-l
Scaling Lower Limit
0
alt3
M
dp
Decimal Point
0
For input type of analog
c
alh3
M
Temperature Unit
d-u
°C, °F
For input type of
c
tr-t
temperature
M
sl-h
SP Upper Limit
c
1300.0
tr-h
M
Limit the set point
100.0
c
sl-l
SP Lower Limit
-200.0
tr-l
M
cntl
PID ON/OFF
o1-t
pid
M
4-20
Standard or
s-hc
Heating/Cooling
stnd
ev-b
M
ST (Self-tuning)
st
For input type of
on
temperature, stand-
ev-1
ard control, or PID
M
none
ptrn
Program Pattern
off
ev-2
M
stop
pbnk
Valid Program Bank
When assigning PID or
7
ev-3
control output to ON/OFF
M
output
none
cp
Control Period (Heating)
20
ev-4
Set the ON/OFF
M
output cycle.
none
Control Period (Cooling)
c-cp
20
clfl
M
flot
orev
Direct/Reverse Operation
or-r
calb
M
alt1
Alarm 1 Type
2
mot
M
c
alh1
Alarm 1
Hysteresis
0.2
sqr
M
amov
Appendix
Alarm 2 Type
2
M
Alarm 2
Hysteresis
0.2
M
Alarm 3 Type
2
M
Alarm 3
Hysteresis
0.2
M
Transfer Output Type
Linear output
off
M
Transfer Output
Upper Limit
M
Transfer Output
Lower Limit
0.0
M
Linear Current Output
Linear output
M
Bank Numbers Used
1
M
Event Input
Assignment 1
M
Event Input
Assignment 2
M
Event Input
Assignment 3
M
Event Input
Assignment 4
M
Closed/Floating
M
Motor Calibration
off
M
Travel Time
30
M
Extraction of Square
Root Enable
off
M
Move to Advanced Function
Setting Level:
Displayed when initial set-
ting/ communications pro-
0
tect is set to 0.
M
Move by setting password (−169).