Omron E5AN-H User Manual page 240

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

PID Setting Level
PID * Cooling Coefficient
*.csc
(*: 1 to 8)
Function
Setting
See
See
PID * LBA Detection Time
*.lba
(*: 1 to 8)
Function
Setting
See
See
If the heating and cooling characteristics of the control object are very differ-
ent and good control characteristics cannot be achieved with the same PID
constants, the cooling coefficient can be used to adjust the proportional band
(P) for the control output assigned to the cooling side. One parameter is set
for each PID set.
• In heating/cooling control, the proportional band P for the cooling control
output is calculated using the following formula to set the cooling coeffi-
cient:
Cooling control output side P = Cooling coefficient × P (proportional band)
• The cooling coefficient will be set automatically if autotuning is executed
when the Automatic Cooling Coefficient Adjustment parameter is set to
ON. The execution results will be saved in the PID set where autotuning
was started. If non-linearity is strong in the cooling characteristics, how-
ever, this function may not find the optimum cooling coefficient.
Setting range
0.01 to 99.99
■ Related Parameters
PID (*) proportional band (PID setting level): Page 217
These parameters set whether the LBA function is to be enabled or disabled
and sets the time interval for detection, for each PID set.
• These parameters set the time interval for detecting the LBA.
• Setting 0 disables the LBA function.
• For ON/OFF control, make the setting in the LBA Detection Time parame-
ter in the advanced function setting level.
Setting range
0 to 9999
■ Related Parameters
Alarm 1 type (initial setting level): Page 231
LBA level (advanced function setting level): Page 259
LBA band (advanced function setting level): Page 260
Heating and cooling control and 2-
PID control must be used.
Unit
Default
None
1.00
2-PID control must be used.
Alarm 1 must be assigned.
The alarm 1 type must be 12 (LBA).
Unit
Default
s
0
Section 5-6
219

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h

Table of Contents