Setting Control Specifications
4-3-4

Setting the Set Point

Water
cooling
100
0
MV % (cooling)
Note
When using a relay for cooling output, the minimum output ON/OFF width can
be used to prevent relay degradation. For details on this setting, refer to
page 58.
These parameters set the set point.
Variable type
D0/90
Note
The decimal point position is determined by the sensor selection.
Refer to 4-7-1 Bank Function for details on banks.
Set the set point so that it is within the input range as well as the set point lim-
iter range.
If the set point is out-of-range, the internal set point actually used for control
will be limited to a value within the input range and set point limiter range.
■ Set Point Limiter
These parameters apply a limit to the set point's setting range so that the con-
trol subject does not reach an abnormal temperature.
Variable type
D5/95
Conditions for use
Note
The decimal point position is determined by the sensor selection.
Set the SP Upper and Lower Limits within the input range and also set the SP
Upper Limit > SP Lower Limit.
If the SP Lower Limit > SP Upper Limit, the larger value will function as the SP
Upper Limit. In addition, if the limit range is set outside of the input range, it
will be limited to the input range.
The SP will not be changed automatically, even if the input type or SP Limiter
is changed. Although the SP will not be changed automatically, the internal
SP used for control will be limited to the input range or SP Limiter (whichever
range is narrower).
Air
cooling
Linear
100
Parameter name
Set point
(BANK)
Parameter name
SP Upper Limit
(Channel)
SP Lower Limit
(Channel)
No special conditions
Section 4-3
Setting range
Default
1999 to 9999 EU
0
Setting range
Default
1999 to 9999 EU
9999
1999 to 9999 EU
1999
71