Setting the Set Point (SP)

3-6

Setting the Set Point (SP)

Operation Level
C
20
0
Operation Level
C
20
0
50.0
3-6-1

Changing the SP

Operating Procedure
Operation Level
C
30
0
C
30
200
• When "open in alarm" is set for the alarm 1 output, the open in alarm sta-
tus is also applied to heater burnout, HS alarm, heater overcurrent, and
input error outputs.
Auxiliary output
functions 1 to 3
Close in Alarm ON
OFF
Open in Alarm
ON
OFF
• The alarm output will turn OFF (i.e., the relay contacts will open) when
power is interrupted and for about two seconds after the power is turned
ON regardless of the setting of the Auxiliary Output 1 to 3 Open in Alarm
parameter.
The operation level is displayed when the power is turned ON. The process
value (PV) is at the top of the display, and the set point (SP) is at the bottom.
For Controllers that support a No. 3 display (E5AN/E5EN), the contents set
in the PV/SP Display Screen Selection parameter (advanced function setting
level) are displayed below the PV and SP.
The MV is displayed as the default. For details, refer to 3-11 Setting the No.
3 Display.
• The set point cannot be changed when the Operation/Adjustment Protect
parameter is set to 3. For details, refer to 4-9 of H156 Using the Key Pro-
tect Level.
• To change the set point, press the U or D Key in the Process Value/Set
Point parameter (in the operation level), and set the desired set value. The
new set point is selected two seconds after you have specified the new
value.
• Multi-SP is used to switch between two or four set points. For details, refer
to 4-5 of H156 Using Event Inputs for details.
In this example, the set point is changed from 0°C to 200°C.
1. Normally, the Process Value/Set Point parameter is displayed. The set
point is 0°C.
2. Use the U and D Keys to set the set point to 200°C.
Section 3-6
Auxiliary
Indicators
output
(SUB1 to SUB3)
ON
Lit
OFF
Not lit
OFF
Lit
ON
Not lit
39