Setting The Set Point (Sp); Changing The Sp - Omron E5CC User Manual

Digital
Hide thumbs Also See for E5CC:
Table of Contents

Advertisement

4 Basic Operation
4-7

Setting the Set Point (SP)

Operation Level
20
0
20
0
50.0
4-7-1

Changing the SP

• The set point cannot be changed when the Operation/Adjustment Protect parameter is set to 3. For
details, refer to 5-7 Using the Key Protect Level.
• To change the set point, press the U or D Key in the PV/SP parameter (Operation Level) or for the
SP/SP (character display) display in the Operation Level, and set the desired set value. The new set
point is selected three seconds after you have specified the new value.
• Multi-SP is used to switch between eight set points. For details, refer to 5-4 Using Event Inputs for
details.
In this example, the set point is changed from 0°C to 200°C.
Operating Procedure
1
Press the U or D Key in the Operation Level to set the SP to
200. The default SP is 0°C.
Additional Information
• If there are a lot of digits in a numeric value, you can use the S (Shift Key) to select the digit to
change before you change the value of the digit.
Example: Changing 1,000°C to 1,200°C
4 - 20
The Operation Level is displayed when the power is turned ON. For the default
setting, the No. 1 display shows the PV, the No. 2 display shows the SP, and the
No. 3 display (E5EC/E5AC only) shows the MV.
The contents that is set in the PV/SP Display Screen Selection parameter in the
Advanced Function Setting Level are displayed.
For details, refer to 4-13-1 PV/SP Display Selections.
1
Press S Key three times.
The third digit will flash.
2
Press the U Key to set the value to 1200.
Operation Level
30
200
Operation Level
30
1000
Operation Level
30
1200
E5@C Digital Temperature Controllers User's Manual (H174)