Using the Transfer Output
Transfer Output
Destination
Transfer Output Type
Note
• The operation differs for models with a transfer output and models without
a transfer output for which control output 1 or control output 2 is used as a
simple transfer output, as shown in the following table.
Transfer
Control output 1
output
Yes
---
No
Current output or linear
voltage output
No
Current output or linear
voltage output
No
Relay output, voltage
output (for driving
SSR), or SSR output
No
Relay output, voltage
output (for driving
SSR), or SSR output
Precision and User Calibration
Transfer output
Simple transfer out-
put
Note For details on the calibration method, refer to SECTION 6 CALI-
BRATION.
Transfer output type
OFF (See note 1.)
Set point
Set point during SP ramp sp-m
PV
MV monitor (heating)
(See note 4.)
MV monitor (cooling)
(See note 5.)
Valve opening (See note
6.)
(1) The default is OFF. For a Controller that does not support a transfer out-
put, the item specified for the Control Output 1 Assignment or Control
Output 2 Assignment parameter will be output.
(2) The output value will be different between when the Transfer Output Type
parameter is set to a heating control output or cooling control output, and
when the Control Output 1 Assignment or Control Output 2 Assignment
parameter is set to a heating control output or cooling control output.
Example: When a Current Output Is Set to 4 to 20 mA and MV Monitor
(Heating) Is Selected
When used as a transfer output, 4.0 mA will be output for 0% and
20.0 mA will be output for 100%.
Control output 2
---
None, relay output, voltage
output (for driving SSR), or
SSR output
Current output or linear
voltage output
Current output or linear
voltage output
None, relay output, voltage
output (for driving SSR), or
SSR output
Precision
±0.3% FS
Not specified.
Symbol
off
---
sp
SP lower limit to SP upper limit
SP lower limit to SP upper limit
pv
Input setting range lower limit to input set-
ting range upper limit or
Scaling lower limit to scaling upper limit
mv
−5.0 to 105.0 (heating/cooling control: 0.0 to
105.0) (See note 2.)
c-mv
0.0 to 105.0 (See note 2.)
v-m
−10.0 to 110.0
Section 4-14
Transfer output
destination
Transfer output
Control output 1
Control output 1
Control output 2
None
User calibration
Supported. (See note.)
Not supported.
Setting range
125