Advanced Function Setting Level
Setting
See
See
rsph
Remote SP Upper Limit
rspl
Remote SP Lower Limit
Function
Setting
See
See
• When this parameter is set to OFF, only the local SP can be used. In addi-
tion, the Set Point During SP Ramp parameter is enabled only when the
SP ramp function is set to ON.
Setting range
ON: Enabled, OFF: Disabled
■ Related Parameters
Set point during SP ramp (operation level): Page 180
SP mode (adjustment level): Page 193
• This parameter sets the upper and lower limits for a remote SP. An upper
limit of 20 mA and a lower limit of 4 mA are supported. Set the upper limit
in the Remote SP Upper Limit parameter, and set the lower limit in the
Remote SP Lower limit parameter.
RSP
Upper limit
Lower limit
4
• When the SP Upper Limit or SP Lower Limit parameter setting is
changed, the remote SP upper or lower limit is forcibly changed to that
setting.
Setting
Remote SP
SP lower limit to SP upper limit
Upper Limit
Remote SP
SP lower limit to SP upper limit
Lower Limit
■ Related Parameters
Decimal point (initial setting level): Page 226
SP upper limit, SP lower limit (initial setting level): Page 227
Remote SP enable (advanced function setting level): Page 266
off
The ST parameter must be set to
OFF. The Remote SP Enable param-
eter must be set to ON.
Input (mA)
20
Setting range
Section 5-10
Default
Unit
Default
EU
1300.0
−200.0
EU
267