Proportional band (P)
Integral time (I)
Derivative time (D)
Control Period
Manual reset value
Alarm setting range
Sampling period
Insulation resistance
Dielectric strength
Malfunction vibration
Vibration resistance
Malfunction shock
Shock resistance
Weight
E5CN-H
E5AN-H
E5EN-H
Degree of protec-
E5CN-H
tion
E5AN-H
E5EN-H
Memory protection
(1) The indication accuracy of K thermocouples in the −200 to 1,300°C range, T and N thermocouples
Note
at a temperature of −100°C or less, and U and L thermocouples at any temperature is ±2°C ±1 digit
maximum. The indication accuracy of B thermocouples at a temperature of 400°C to 800±3°C or
less is not specified. The indication accuracy of R and S thermocouples at a temperature of 200°C
or less is ±3°C ±1 digit maximum. The indication accuracy of W thermocouples is (the larger of
±0.3% or ±3°C) ±1 digit maximum and the indication accuracy of PLII thermocouples is (the larger
of ±0.3% or ±2°C) ±1 digit maximum.
(2) Ambient temperature: −10°C to 23°C to 55°C
Voltage range: −15 to +10% of rated voltage
Temperature Input
Analog Input
Standard, heating/cooling, position proportional (closed): 0.0 to 3240.0
Position proportional (floating): 0.1 to 3240.0 (in units of 0.1 s)
0.0 to 3240.0 (in units of 0.1 s)
0.5, 1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
−19,999 to 32,400 (decimal point position depends on input type)
60 ms
20 MΩ min. (at 500 VDC)
2,300 VAC, 50/60 Hz for 1 min between terminals of different charge
2
10 to 55 Hz, 20 m/s
for 10 min each in X, Y and Z directions
2
10 to 55 Hz, 20 m/s
for 2 hr each in X, Y, and Z directions
2
100 m/s
, 3 times each in X, Y, and Z directions
2
300 m/s
, 3 times each in X, Y, and Z directions
Approx. 150 g
Approx. 310 g
Approx. 260 g
Front panel: IP66
Rear case: IP20
Terminals: IP00
EEPROM (non-volatile memory) (number of writes: 1,000,000)
0.1 to 3240.0°C or °F
(in units of 0.1°C or °F)
0.1% to 999.9% FS (in units of 0.1% FS)
Adapter: approx. 10 g
Adapter: approx. 100 g
Appendix
Terminal cover: approx. 10 g
Terminal cover: approx.
1.6 g per cover
299