Using Banks and PID Sets
Automatic PID Set Selection
Automatic selection
PID set
range
1
200.0
2
400.0
PV: 240.0
3
500.0
(upper limit)
4
600.0
5
700.0
6
800.0
7
1000.0
8
1300.0
130
Parameter
Integral Time
Standard, heating/cooling,
position proportional (closed):
0.0 to 3,240.0
Position proportional (float-
ing): 0.1 to 3,240.0
Derivative Time
0.0 to 3240.0
MV Upper Limit
Standard: MV lower limit + 0.1
to 105.0
Heating/cooling: 0.0 to 105.0
Position proportional (closed):
MV lower limit + 0.1 to 105.0
Standard: −5.0 to MV upper
MV Lower Limit
limit −0.1
Heating/cooling: −105.0 to 0.0 −105.0
Position proportional (closed):
−5.0 to MV upper limit −0.1
Temperature: −19,999 to
Automatic Selection
Range Upper Limit
32,400
Analog: −5.0 to 105.0
Cooling Coefficient
0.01 to 99.99
LBA Detection Time
0 to 9,999 (0: LBA function
disabled)
Note When the PID Automatic Selection Data parameter is set to DV, the
unit will be %FS.
The settings for the PID sets are made in the PID setting level. In the PID set-
ting level, select the PID set numbers to be edited with the Display PID Selec-
tion parameter, and make the settings for each PID set.
Parameter
Display PID Selection
Note The current PID set is displayed. If you use the U and D Keys to
change the PID set, the monitor function will be canceled
When the following parameters are changed, the changes will be reflected in
the current PID set:
Proportional Band, Integral Time, Derivative Time, MV Upper Limit, MV
Lower Limit, Cooling Coefficient (adjustment level)
LBA Detection Time (advanced function setting level)
• If the PID Set No. parameter for a bank is set to 0, the PID set will be
selected automatically according to preset conditions.
In the setting example on the left (with the PID Set Automatic Selection Data parame-
ter set to PV), the following PID parameters are used:
PV ≤ 200°C: PID Set No. 1
200°C < PV ≤ 400°C: PID Set No. 2
Set the PID Set Automatic Selection Range Upper Limit so that the set value
becomes larger as the PID set number increases. For PID Set No. 8, however, the
automatic selection range upper limit always equals the upper limit of the specified
range.
The PID Set Automatic Selection Hysteresis parameter can be used to set the hyster-
esis to prevent chattering when changing the PID set.
The PID Set Automatic Selection Data parameter can be used to select PV, DV
(Derivative), or SP.
Setting range
Setting range
Unit
1 to 8
---
Section 4-15
Default
Unit
233.0
s
40.0
s
105.0
%
−5.0
%
−5.0
1320.0
EU
105.0
% (See note.)
1.00
None
0
s
Default
See note.