Advanced Function Setting Level
istp
Input Shift Type
Function
Setting
See
See
mvse
MV at Stop and Error Addition
Function
Setting
See
See
amad
Auto/Manual Select Addition
Function
Setting
256
This parameter sets the shift method for a temperature input.
• When the input type is for a temperature input, set either a 1-point shift or
a 2-point shift.
Setting range
ins1: 1-point shift, ins2: 2-point shift
■ Related Parameters
Temperature input shift, Upper-limit temperature input shift value, Lower-limit
temperature input shift value (adjustment level): Page 199
Input type (initial setting level): Page 224
This parameter sets whether or not the MV at Stop and MV at PV Error
parameters are to be displayed.
• Set whether or not the MV at Stop and MV at PV Error parameters are to
be displayed.
Setting range
on: Displayed, off: Not displayed
■ Related Parameters
MV at stop, MV at PV error (adjustment level): Page 204
• Set whether the Auto/Manual Switch parameter is to be displayed.
Setting range
on: Displayed, off: Not displayed
Note For Controllers with a PF Key (E5AN/EN-H), the default is ON.
Section 5-10
The input type must be for a temper-
ature input.
Default
ins1
The control must be set to 2-PID
control.
Default
off
The control must be set to 2-PID
control.
Default
on