Bank Setting Level
See
See
*.spr
Bank 0 to 7 SP Ramp Set Value
Function
Setting
See
See
Bank * Alarm Value 1
*.a-1
(*: 0 to 7)
Function
Setting
■ Related Parameters
PID (*) proportional band, PID (*) integral time, PID (*) derivative time (PID
setting level): Page 217
PID (*) automatic selection range upper limit (PID setting level): Page 218
PID set automatic selection data (advanced function setting level): Page 269
These parameters are used to set the SP ramp set value for each bank.
• The SP ramp set value can be set for banks 0 to 7.
• This parameter specifies the rate of change during SP ramp operation.
Set the maximum allowable change width per unit of time as the SP ramp
set value. When this parameter set to OFF, the SP ramp function will be
disabled.
• During temperature input, the decimal point position for the SP ramp set
value depends on the current sensor, and during analog input it depends
on scaling.
Setting range
OFF, 1 to 32400
■ Related Parameters
Input type: Page 224
Scaling upper limit, Scaling lower limit, Decimal point: Page 226
ST (initial setting level): Page 228
SP ramp time unit (advanced function setting level): Page 244
These parameters set one of the input values "X" in the alarm type list for
each bank.
• These parameters set the value for alarm value 1 in banks 0 to 7.
• During temperature input, the decimal point position is set automatically
according to the current sensor, and during analog input it depends on the
Decimal Point parameter setting.
Setting range
−19999 to 32400
Unit
EU/s, EU/min, EU/h
Unit
Default
EU
0.0
Section 5-5
The ST parameter must be set to
OFF.
Default
OFF
Alarm 1 must be assigned.The
alarm 1 type must not be 0, 1, 4, 5,
or 12.
211