Omron E5AN-H User Manual page 284

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Advanced Function Setting Level
sub1
Auxiliary Output 1 Assignment
Function
Setting
Note
See
See
• This parameter sets the function to be assigned to auxiliary output 1.
none: No function is assigned to auxiliary output 1.
o:
Heating control output is output.
c-o:
Cooling control output is output. (See note 1.)
alm1: Alarm 1 is output.
alm2: Alarm 2 is output.
alm3: Alarm 3 is output.
p.end: Program end is output. (See note 2.)
ralm: Control output ON/OFF count alarm
wr1:
Work bit 1 (See note 4.)
wr2:
Work bit 2 (See note 4.)
wr3:
Work bit 3 (See note 4.)
wr4:
Work bit 4 (See note 4.)
wr5:
Work bit 5 (See note 4.)
wr6:
Work bit 6 (See note 4.)
wr7:
Work bit 7 (See note 4.)
wr8:
Work bit 8 (See note 4.)
(1) If c-o is assigned for standard control, a value equivalent to 0% will be
output.
(2) Can be selected when the Program Pattern parameter is set to OFF, but
the function will be disabled.
(3) If a setting is changed when the Program Pattern parameter is not set to
OFF, control automatically switches to p.end.
(4) WR1 to WR8 are not displayed when the logic operation function is not
used.
■ Related Parameters
Program pattern (initial setting level): Page 229
Auxiliary output 1 must be assigned.
Setting range
Section 5-10
Default
alm1
(See note
3.)
263

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h

Table of Contents