Advanced Function Setting Level
hsl
HS Alarm Latch
Function
Setting
See
See
hsh
HS Alarm Hysteresis
Function
Setting
See
See
258
• When this parameter is set to ON, the HS alarm is held until any of the fol-
lowing conditions is satisfied.
a
The HS alarm current is set to 50.0 A.
b
The power is cycled.
c
The latch is cancelled by the PF Key.
(PF Setting = LAT: Alarm Latch Cancel)
d
The latch is cancelled by an event input.
(Event Input Assignment 1 to 4 = LAT: Alarm Latch Cancel)
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
Setting range
on: Enabled, off: Disabled
■ Related Parameters
HS alarm use (advanced function setting level): Page 257
Event input assignment 1 to 4 (initial setting level): Page 238
HB ON/OFF: Page 246, PF setting: Page 273 (advanced function setting
level)
• This parameter sets the hysteresis for HS alarms.
Setting range
0.1 to 50.0
A
■ Related Parameters
HS alarm use (advanced function setting level): Page 257
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
Alarm 1 must be assigned.
The HS Alarm parameter must be
set to ON.
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The HS Alarm parameter must be
set to ON.
The HS Alarm Latch parameter must
be set to OFF.
Unit
Default
0.1
Section 5-10
Default
OFF