Operation Level
prst
Program Start
Function
Operation
See
See
sktr
Soak Time Remain
Function
Monitor
See
See
184
This parameter starts and stops the simple program function.
• The RUN/STOP status will automatically switch to RUN when this param-
eter is set to STRT.
• The simple program will stop when this parameter is set to RSET.
• This parameter will function as a monitor display for the start/stop status
of the simple program if an event input is selected to start the simple pro-
gram.
Setting range
RSET
Stops the simpler program.
STRT
Starts the simpler program.
■ Related Parameters
Soak time remain: Page 184, RUN/STOP: Page 185 (operation level)
Bank * soak time, Wait band (bank setting level): Page 215
Program pattern (initial setting level): Page 229
Soak time unit (advanced function setting level): Page 266
• This parameter measures and displays the remaining time of the soak
time for the simple program function.
Monitor range
0 to 9999
■ Related Parameters
Program start (operation level): Page 184
Bank * soak time, Wait band (bank setting level): Page 215
Program pattern (initial setting level): Page 229
Soak time unit (advanced function setting level): Page 266
The Program Pattern parameter
must not be set to OFF.
Default
rset
The Program Pattern parameter
must not be set to OFF.
Unit
min or h
Section 5-3