Set Point 0 (Sp-0), Set Point 1 (Sp-1); Temperature Input Shift (Ins) - Omron E5ZN Operation Manual

Hide thumbs Also See for E5ZN:
Table of Contents

Advertisement

Adjustment Level
7-4-5
Set Point 0 (sp-0
Set Point 1 (sp-1
Function
Communications
Settings
See Also
7-4-6
Temperature Input Shift (ins
Function
Communications
Settings
sp-0)
sp-0
sp-0
sp-1)
sp-1
sp-1
Condition: The "number of multi-SP uses" parameter must be set to
either 1 or 2, and the "multi-SP uses" parameter must be set to ON.
These parameters set the set points when the multi-SP function is used.
The values set in these parameters can be selected.
• When the set point has been changed, the set value of these parameters
currently set by multi-SP is linked and changed.
• The decimal point position is dependent on the selected sensor.
During analog input, the decimal point position is dependent on the setting of
the "decimal point position" parameter.
Setting
Set point 0
Set point 1
Lower set point limit to upper set point limit
• Related Parameters
"Number of multi-SP uses" (advanced function setting level) (page 135)
"Event input allocation" "Multi-SP uses" (advanced function setting level)
(page 135)
"PV/SP" (operation level) (page 115)
"Input type" (initial setting level) (page 128)
ins)
ins
ins
Condition: The "additional temperature input display" parameter must be
set to ON and the "input type" parameter must not be set to temperature
input for a non-contact temperature sensor.
Sometimes an error between the set point and the actual temperature occurs.
To offset this, a value obtained by adding an input shift value to the input is
displayed as the measurement value and used for control.
The entire input range is shifted by a fixed rate (1-point shift). If the input shift
value is set to -1.0 ° C, the set point is controlled to a value obtained by sub-
tracting 1.0 ° C from the actual temperature.
ch
1
2
FFFFF831H to 0000270FH (-199.9 to 999.9)
ch
1
2
1
2
Setting range
Variable type
C1
C1
Setting range
Section 7-4
Variable type
Address
C1
000D
C1
010D
C1
000E
C1
010E
Unit
EU
Address
000F
010F
Unit
°C or °F
Default
0
Default
0.0
123