Counting Control Output ON/OFF Operations
Control Output ON/
OFF Counter Monitor
Function
Control Output ON/
OFF Count Alarm
Function
Control Output 1 ON/OFF Alarm Set
Value
Control Output 2 ON/OFF Alarm Set
Value
ON/OFF Counter Reset Function
ON/OFF Counter Reset
Note
This function is not displayed when the Control Output 1 ON/OFF Alarm Set
Value and the Control Output 2 ON/OFF Alarm Set Value parameter are set to
0, or when the control outputs are set for linear outputs.
Parameter name
Control Output 1 ON/OFF Count Monitor
Control Output 2 ON/OFF Count Monitor
Display When ON/OFF Count Alarm Occurs
When an ON/OFF count alarm occurs, the PV display in the No. 1 display
shown below alternates with the ralm display on the No. 2 display.
• PV
• PV/SP (Including the items displayed by setting the "PV/SP" Display
Screen Selection parameter.)
• PV/Manual MV (Valve Opening), PV/SP/Manual MV (Valve Opening)
• PV/SP displayed for the monitor/setting items
Normal
C
PV/SP
If the ON/OFF counter exceeds the control output ON/OFF count alarm set
value, an ON/OFF count alarm will occur. The alarm status can be assigned
to a control output or an auxiliary output, or it can be displayed at the Control-
ler. The ON/OFF count alarm set value function is disabled by setting the ON/
OFF count alarm set value to 0.
Parameter name
The ON/OFF counter can be reset for a specific control output.
Parameter name
0: Disable the counter reset
function.
1: Reset the control output 1
ON/OFF counter.
2: Reset the control output 2
ON/OFF counter.
After the counter has been reset, the control output ON/OFF count monitor
value will be automatically returned to 0.
If an error occurs in the control output ON/OFF counter data, the ON/OFF
count monitor value will be set to 9999 and an ON/OFF count alarm will occur.
The alarm can be cleared by resetting the ON/OFF counter.
Setting range
0 to 9999
0 to 9999
ON/OFF Count Alarm
C
25.0
25.0
100.0
ralm
Setting range
0 to 9999
0 to 9999
Setting range
Section 4-21
Unit
Default
100 times
0
100 times
0
Alternating
display
100.0
Unit
Default
100 times
0
100 times
0
Unit
Default
---
0
151